| Specifications |
|
Door position
|
Voltage (V)
|
Error detecting
|
| Vent | 0.3 ± 0.15 | Low voltage : 0.1V or less High voltage : 4.9V or more |
| Defrost | 4.7 ± 0.15 |
DescriptionThe mode control actuator is located at the heater unit.It adjusts the position of the mode door by operating the mode control actuator based on the signal of the A/C control unit.
Inspection1.Turn the ignition switch OFF.2.Disconnect the mode control actuator connector.3.Verify that the mode control actuator operates to the defrost mode when connecting 12V to terminal 3 and grounding terminal 4.